MAN0868-04-EN Specifications / Installation
__________________________________________________________________________________________________________________________________________________________________
12/19/2008 Page 1 of 3 ECN # 947
1 Specifications
Specifications
General Specifications
Required
Power
(Steady State)
130 mA @ 24 VDC
Required
Power (Inrush)
30 A for 1 ms @ 24 VDC
Primary Power
Range
10 – 30 VDC
Relative
Humidity
5 to 95% Non-condensing
Clock Accuracy +/- Seven Minutes/Month at 20C
Operating
Temperature
-10°C to +60°C
Terminal Type Screw Type, 5 mm Removable
Weight 12 oz. (340.19 g)
CE
UL
See Compliance Table at :
http://www.heapg.com/Support/compliance.htm
2 Panel Cut-Out and Dimensions
Note: Max. panel thickness: 5 mm.
Refer to the User Manual for panel box information and a handy
checklist of requirements.
Note: The tolerance to meet NEMA standards is ± 0.005” (0.1 mm).
3 Ports / Connectors / Cables
Note: The case of the XLt is black, but for clarity, it is shown in a lighter gray color.
XLt OCS Model:
HE-XT100 / HEXT240C000
/
HEXT240C100
3.622 [92mm]
3.622 [92mm]
001XLE002
Power Connector
Power Up:
Connect to Earth Ground.
Apply 10 - 30 VDC.
Screen lights up.
Torque rating 4.5 – 7 Lb-In
(0.50 – 0.78 N-m)
CAN Connector
Use the CAN Connector when
using CsCAN network.
Torque rating 4.5 – 7 Lb-In
(0.50 – 0.78 N-m)
To Remove Back Cover:
Unscrew 4 screws located on
the back of the unit and remove
back cover.
CAUTION: Do not over tighten
screws when replacing back
cover.
Memory Slot:
Uses Removable Memory for
data logging, screen captures,
program loading and recipes.
Horner Part No.: HE-MC1
Serial Communications:
MJ1: (RS-232 / RS-485) Use for
Cscape programming and
Application-Defined
Communications.
MJ2: (RS-232 / RS-485) Use for
Application-Defined
Communications.
MJ1
(RS-232 / RS-485)
MJ2
(RS-232 / RS-485)
Memory Slot
NET 1
(CsCAN)
Powe
r
DIP
Switch
Note – Your keypad overlay
appearance may differ. Standard
US/EU overlays pictured here for
example.
Vedere la pagina 0
1 2 3

Sommario

Pagina 1 - HEXT240C100

MAN0868-04-EN Specifications / Installation ____________________________________________________________________________________________

Pagina 2 - Signal Direction

MAN0868-04-EN Specifications / Installation ____________________________________________________________________________________________

Pagina 3

MAN0868-04-EN Specifications / Installation ____________________________________________________________________________________________

Commenti su questo manuale

Nessun commento