MAN0951-02 12 May 2011 PAGE 5
HE-579ACM300
Information is subject to change without notice.
Consumed Analog Data – This data is sent from the controller to the SmartBlock. For typical
applications the I/O configuration setup in Cscape will automatically populate this data. For more
advanced applications you may use NetPut functions to write this data. Please see the advanced
programming guide MAN0880 for more details.
Voltage Input Ratio
For example 120 to 480 step up enter 0.25
for 7200 to 480 step down enter 15
Current Input Ratio
For example for 5A:100A CT enter 20
Phase correction for CTs Enter in degrees
Min of -1.63° Lag, Max of +3.32 Lead
Seconds for zero cross alarm – max 2.5
Voltage Sag level in volts
Number of half cycles before alarm
Number of half cycles before alarm
Voltage level for peak alarm
Current level for peak alarm
Produced Analog Data – This data is sent from the SmartBlock to the controller. Normally this data is
mapped into specific registers in the I/O configuration in Cscape. For advanced applications NetGet
functions can be used to obtain this data. Since this data is broadcast to all controllers on the network
additional controllers can use NetGet functions to obtain this data as well.